Seite 1 - Addendum 95-8577

Addendum 95-8577HART® Communication with the X3301Multispectrum IR Flame Detector3.1 Rev: 10/13 95-8577

Seite 2 - Table Of Contents

95-857783.1HART PV MENU1) PV Unit Not implemented for X3301.2) PV Not implemented for X3301.3) PV SNSR Unit Not implemented for X3301.4) PV USL No

Seite 3 - HART Communication

9 95-85773.1CONDENSED STATUS1) Xmtr Addstatus 0 Fire Alarm oi Cal Active Manual oi Active Warmup2) Xmtr Addstatus 1 Spare3) Xmtr Addstatus 2 Fault A

Seite 4 - 3301 IR DETECTOR

95-8577103.1STATUS INFO MENUThis menu (read only) shows extensive status information about the detector.1) Warmup (Y/N) Device is in the power-up tim

Seite 5 - 3 95-8577

11 95-85773.1HARDWARE MENU1) Heater Power Actual heater power (0 to 100%). Heater prevents condensation and icing on the detector optics.2) Heater S

Seite 6 - HART MENU STRUCTURE

95-8577123.1oi MENU1) Left oi Percentage of calibrated oi test signal returned by the left sensor. Reading should be 90 to 100 percent. If reading is

Seite 7 - 20 mA, fire alarm

13 95-85773.1DETECTOR SETTINGSThis menu shows factory settings relating to relay operation, detector sensitivity and response.1) Fire Relay (L/NL) Fi

Seite 8 - General Info Menu

95-8577143.1COMMAND MENUThe Command Menu allows the operator to initiate a manual oi test and also to perform various reset/clear functions.1) Start P

Seite 9 - 7 95-8577

15 95-85773.1HART CMD MENUThe HART CMD (Command) Menu allows the operator to perform diagnostic and service functions as follows:1) Self Test Interna

Seite 10 - X3301 Root Menu

95-8577163.1CONFIGURATION MENU1) Edit Cons oi Fails This option allows the operator to select the number of consecutive oi failures before an oi faul

Seite 11 - 0 Fire Alarm

17 95-85773.1WRITE PROTECTThis function enables the operator to enable/disable password and write protection capability, as well as to enter or change

Seite 12 - 20 mA, fire alarm

Table Of ContentsInterconnecting the HART Communicator with the Detector ...1HART Device Description Language ...3Detector W

Seite 13 - 40°F to +167°F

95-8577183.1SET REAL TIME CLOCKTo set the real time clock, enter the current time and date information into the appropriate fields.1) Seconds 0 to 59

Seite 14 - Status Info Menu

Detector Electronics Corporation6901 West 110th Street Minneapolis, MN 55438 USAT: 952.941.5665 or 800.765.3473F: 952.829.8750W: http://www.det-troni

Seite 15

Digital communication with the X3301 allows the operator to monitor the status of the detector, determine factory settings, adjust field settings, and

Seite 16 - 4-20mA loop are “live”

95-857723.124 VDCmAPLC–+600 W MAX*AT 24 VDC–+B2262987654321191817161514131211mA +mA + REFmA –24 VDC +24 VDC –292827262524232221X3301 IR DETECTORFigure

Seite 17 - 4 to 20 mA) to a

3 95-85773.1Multidrop ModeOptical flame detectors are life safety devices and require the 4-20 mA loop for transmitting important detector status data.

Seite 18 - 4 to 20 mA span factor

95-857743.1HART MENU STRUCTURECommand Menu1) Start Passive oi2) Start Active oi3) Clear oi Fault4) Reset Latches5) Master Reset6) Clear Data Log

Seite 19

5 95-85773.1X3301 ROOT MENUWhen HART communication is established, the first menu displayed is the X3301 Root menu:1) Fire (Yes/No) Indicates “Y” if

Seite 20 - Device Setup Menu

95-857763.1GENERAL INFO MENU1) Manufacturer Det-Tronics.2) Model X3301.3) Serial Number Serial number of device.4) Part Number Manufacturer’s part n

Seite 21 - 95-8577

7 95-85773.1HART INFO MENU1) Universal Rev HART universal revision.2) Field Device Rev HART field device revision.3) Final Asmbly No. A number that