Instructions 95-8562Dual Spectrum®Infrared Flame DetectorPM-5MPX4.1 Rev: 8/13 95-8562
8 95-85624.1APPENDIX AFM APPROVAL DESCRIPTION AND PERFORMANCE REPORTHAZARDOUS LOCATION RATINGS• Intrinsically safe for Class I, II, III, Div. 1, Group
9 95-85624.1FM Approval Description and Performance Report – ContinuedFALSE ALARM IMMUNITY COMBINED WITH FIRE SOURCEFalse Alarm SourceFalse AlarmSourc
10 95-85624.1APPENDIX BCONTROL DRAWING CONFIGURATIONFigure B1—Control Drawing Conguration (Drawing No. 420031)PM-5MPX CONTROL DRAWING CONFIGURATION
11 95-85624.1APPENDIX CINTRINSICALLY SAFECLASS B, STYLE B WIRINGHazardous (Classied) Locations:Class I, Division 1, Group C, DClass I, Division 2, Gr
12 95-85624.1APPENDIX DNONINCENDIVECLASS B, STYLE B WIRINGHazardous (Classied) Locations:Class I, Division 2, Group A, B, C, DClass II, Division 2, G
13 95-85624.1PM-5MPXPM-5MPXPM-5MPXV+ (RED)V+ (ORG)PWR RTN (BLK)PWR RTN (BRN)ALARM + (YEL)ALARM + (GRN)ALARM – (BLU)ALARM – (VIO)TROUBLE + (GRY)TROUBLE
14 95-85624.1APPENDIX FPSS-MP TEST LAMPFigure F1—PSS-MP Test LampLAMP REPLACEMENTREPLACE XENON LAMP MODULE WITH PN 18801 (UNDERWATER KINETICS).WARNING
Detector Electronics Corporation6901 West 110th Street Minneapolis, MN 55438 USAT: 952.941.5665 or 800.765.3473F: 952.829.8750W: http://www.det-troni
Table of ContentsAPPLICATION ...1DETECTOR USE IN HAZARDOUS AREAS ...2ELECTRICAL CHARACTERISTICS...2ENVIRONME
IM PORTAN TBe sure to read and understand the entire instruction manual before installing or operating the Model PM-5MPX Detector. Only qualied perso
2 95-85624.1DETECTOR USE IN HAZARDOUS AREASThe PM-5MPX is FM Approved to FM 3260: 2000, intrinsically safe for use in Class I, II, III, Division 1, Gr
3 95-85624.1ENVIRONMENTAL CHARACTERISTICSTEMPERATURE RANGE—Operating: 0°C to +49°C (+32°F to +120°F ).Storage: 0°C to +70°C (+32°F to +158°F).REL
4 95-85624.1FALSE ALARM IMMUNITYThe PM-5MPX is highly resistant to false alarms. However, a fire alarm output due to non-fire stimuli is possible. (R
5 95-85624.1INTRINSICALLY SAFE CIRCUITSIntrinsically safe installations require the use of suitable and approved barriers, an approved fire alarm cont
6 95-85624.13. Interconnection Wiring. Correct interconnection wiring should be checked by disconnecting any wire from the multi-conductor cable were
7 95-85624.1WARNINGA full system test results in an alarm output. This will result in the suppression system being activated if it is not disabled pri