Det-Tronics X9800 Spezifikationen

Stöbern Sie online oder laden Sie Spezifikationen nach Rauchmelder Det-Tronics X9800 herunter. Det-Tronics X9800 Specifications Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 6
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
1. 1 95-86721
SAFETY MANUAL
X2200 UV, X9800 IR, X5200 UVIR
SIL 2 Certied Flame Detectors
1.1 ©Detector Electronics Corporation 2011 Rev : 8/11 95-8672
SAFETY-CERTIFIED FLAME DETECTORS
This manual addresses the specific requirements and
recommendations applicable to the proper installation,
operation, and maintenance of all Safety‑Certified
(SILCertified) X2200 UV, X9800 IR, and X5200
UVIR Flame Detectors. The safety function of the
X2200/X9800/X5200 is to detect a variety of fires
and to provide present alarm status to its relay and
analog outputs. For complete information regarding
performance, installation, operation, maintenance and
specifications, refer to appropriate instruction manual:
X2200 UV Flame Detector 958549
X9800 IR Flame Detector 958554
X5200 UVIR Flame Detector 958546
QUALITY POLICY STATEMENT
All quality assurance control measures necessary for
safety management as specified in IEC 61508 Part 1
have been implemented. The quality management
system of DetTronics is based on the requirements
of EN ISO 9001 and ANSI/ASQC Q9001 through the
application of the United Technologies Company
Achieving Competitive Excellence (ACE) program. In
addition, the Quality Management System complies
with the European ATEX Directive requirements per EN
13980, the International Electrotechnical Commission
requirements per OD005/V2, and the supervised
testing requirements per ISO 17025.
SAFETY MESSAGES
Procedures and instructions in this section may
require special precautions to ensure the safety of
personnel performing the operations. Information that
raises potential safety issues is indicated by the word
Warning. Always read and understand these safety
messages.
WARNING
The X2200, X9800 and X5200 are intended for
use in hazardous environments that may include
explosive levels of ammable gases and vapors.
These products must be properly installed,
operated and maintained. Improper installation
or use could result in an explosion or re resulting
in death or serious injury.
•Donotremovethedetectorcoverinexplosive
environments when device power is on and
circuits are live.
•Detectormustbeproperlyinstalled,andwiring
compartment cover must be fully engaged
to meet hazardous area explosion-proof/
non-incendive requirements.
Seitenansicht 0
1 2 3 4 5 6

Inhaltsverzeichnis

Seite 1 - SAFETY MANUAL

1. 1 95-86721SAFETY MANUALX2200 UV, X9800 IR, X5200 UVIR SIL 2 Certied Flame Detectors 1.1 ©Detector Electronics Corporation 2011 Rev : 8/11 95-867

Seite 2 - 1. 1 95-86722

1. 1 95-86722DESIGNThe X2200/X9800/X5200 flame detector is classified as a Type B smart device according to IEC61508. The standard model provides an

Seite 3 - 1. 1 95-86723

1. 1 95-86723No special installation requirements exist above and beyond the standard installation practices documented in the instruction manual. E

Seite 4 - 1. 1 95-86724

1. 1 95-86724OPERATION, MAINTENANCE, INSPECTION AND PROOF TESTINGTools Required:•Magneticoi test tool (p/n 102740‑002)•Windowcleaner(p/n001680-0

Seite 5 - 1. 1 95-86725

1. 1 95-86725FAULT/FAILURE ACTION PLANIn the event of a non‑alarm condition result with the Mag oi test, the standard Maintenance and Troubleshooting

Seite 6 - 95-8672

PRODUCT CERTIFICATIONSFM, CSA, ATEX, CE, IECEx, and exida.Refer to the Instruction Manual for details.FMEDA Report available.For complete information

Kommentare zu diesen Handbüchern

Keine Kommentare