6.8 1/09 95-8560Software designed for safety systems and the people who use themUser Guide95-8560-6.0

Seite 2 - CONTENTS

1-1Version 6.0INTRODUCTIONALL IMPLIED WARRANTIES ON THIS SOFTWARE PACKAGE, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A

Seite 3

EAGLE QUANTUM PREMIER CONFIG.11-19EAGLE QUANTUM PREMIER CONFIG.Version 6.0To create an output, double click on one of the “slots” in the scrolling lis

Seite 4

11-20EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.Below is the Output Editor dialog box just after opening. A random, unique

Seite 5

EAGLE QUANTUM PREMIER CONFIG.11-21EAGLE QUANTUM PREMIER CONFIG.Version 6.0Sample output configurations Example 1 involves an output to acknowledge an

Seite 6

11-22EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.The configured output #1 is now displayed both in the output list on the left

Seite 7

EAGLE QUANTUM PREMIER CONFIG.11-23EAGLE QUANTUM PREMIER CONFIG.Version 6.0Clicking on the “+” sign left of the “LON” item will expand it revealing the

Seite 8

11-24EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.Select the “Reset” item from the ARM-015 list, fill in the tagname and miscel

Seite 9

EAGLE QUANTUM PREMIER CONFIG.11-25EAGLE QUANTUM PREMIER CONFIG.Version 6.0Example 3 involves creating an output to initiate a manual Optical

Seite 10 - INTRODUCTION

11-26EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.Output Configuration Screen DetailsThe left hand pane uses a scrolling list

Seite 11

EAGLE QUANTUM PREMIER CONFIG.11-27EAGLE QUANTUM PREMIER CONFIG.Version 6.0Delete immediately and permanently erases a slots configuration. This functi

Seite 12

11-28EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.UploadQueries the controller for its configuration and if a complete configura

Seite 13 - INSTALLATION

1-2Version 6.0INTRODUCTIONWhat is S3 Safety System Software (S3) is a complete, high performance Human Machine Interface software package that is desi

Seite 14

EAGLE QUANTUM PREMIER CONFIG.11-29EAGLE QUANTUM PREMIER CONFIG.Version 6.0The “Arrange” button allows movement of the location of the nodes on the sch

Seite 15

11-30EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.CONFIGURATION BAR • POINT COLORCopy/PasteUsed in conjunction with the “

Seite 16

EAGLE QUANTUM PREMIER CONFIG.11-31EAGLE QUANTUM PREMIER CONFIG.Version 6.0Point ColorIf at anytime a field device becomes difficult to view above the bl

Seite 17

11-32EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.CONFIGURATION BAR • CONTROLLER LOGNew DeviceOpens the “Select Point Type” di

Seite 18

EAGLE QUANTUM PREMIER CONFIG.11-33EAGLE QUANTUM PREMIER CONFIG.Version 6.0Controller LogS3 keeps a log of every event ever excecuted by the controller

Seite 19

11-34EAGLE QUANTUM PREMIER CONFIG.PAGE LEFT BLANK INTENTIONALLY

Seite 20 - CONFIGURATION

12-1EAGLE QUANTUM PREMIER DEVICESVersion 6.0ControllerNOTEThis Section is dedicated to the EQP controller and key eld devices it supports. Please be

Seite 21

12-2EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESConfigure a ControllerTo begin controller configuration, double-click on its s

Seite 22

EAGLE QUANTUM PREMIER DEVICES12-3EAGLE QUANTUM PREMIER DEVICESVersion 6.0Port Baud RateThe port speed can be adjusted in standard intervals between a

Seite 23

12-4EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESSerial Ports 1-4These ports can be used for communication with a host de

Seite 24 - Basic Port Configuration

1-3Version 6.0INTRODUCTIONFeaturesUser friendly point and click navigation, with no special keyboard commands to learn. •Menu driven configuration ens

Seite 25 - Version 6.0

EAGLE QUANTUM PREMIER DEVICES12-5EAGLE QUANTUM PREMIER DEVICESVersion 6.0User ParametersThis button opens the “User Parameters...” dialog box allowing

Seite 26 - Serial Port Settings

12-6EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESThe primary reason for this feature is to accommodate instances where the con

Seite 27

EAGLE QUANTUM PREMIER DEVICES12-7EAGLE QUANTUM PREMIER DEVICESVersion 6.0Option BoardThe Eagle Quantum Premier controller is designed to be e

Seite 28 - START MONITORING

12-8EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESAlarmsSelecting this button opens the “Alarms to Monitor...” dialog box. Th

Seite 29

EAGLE QUANTUM PREMIER DEVICES12-9EAGLE QUANTUM PREMIER DEVICESVersion 6.0EQP CONTROLLER • ALARMSAlarmsAllows for the configuration of the alarm and eve

Seite 30

12-10EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESThe definitions of the eleven columns in the “Alarms to Monitor...” dialog bo

Seite 31

EAGLE QUANTUM PREMIER DEVICES12-11EAGLE QUANTUM PREMIER DEVICESVersion 6.0EQP CONTROLLER • ALARMS & EVENTSActive Color/Normal ColorSelect one of f

Seite 32

12-12EAGLE QUANTUM PREMIER DEVICESPAGE LEFT BLANK INTENTIONALLYEAGLE QUANTUM PREMIER DEVICES

Seite 33

12-13EAGLE QUANTUM PREMIER DEVICESVersion 6.0X3301Multi-Spectrum Infrared Flame DetectorThe MIR X3301 is located on the LON/SLC and provides

Seite 34

12-14EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESHeater OpticsUp to 8 watts of power can be utilized to provide heat to th

Seite 35

1-4INSTALLATIONVersion 6.0RequirementsThe minimum S3 workstation hardware requirements are:Computer. The S3 software suite is designed to ru

Seite 36 - PRINTING

EAGLE QUANTUM PREMIER DEVICES12-15EAGLE QUANTUM PREMIER DEVICESVersion 6.0Oi Test FaultThe detector automatically conducts Oi tests to check t

Seite 37

12-16EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESAlarm LED LatchThe tri-color LED on the face of the detector turns red when

Seite 38

EAGLE QUANTUM PREMIER DEVICES12-17EAGLE QUANTUM PREMIER DEVICESVersion 6.0PV DeadbandA field is provided to enter the desired PV (Process Variable) Dea

Seite 39

12-18EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESUser Levels The “User Level Editor...” provides a means for limiting

Seite 40 - Overview of features

EAGLE QUANTUM PREMIER DEVICES12-19EAGLE QUANTUM PREMIER DEVICESVersion 6.0X3302Multi-Spectrum Infrared Flame DetectorThe MIR H2 X3302 is located on th

Seite 41 - Alarm Logs (DCD Disk Log)

12-20EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESHeater OpticsUp to 8 watts of power can be utilized to provide heat to th

Seite 42 - Configuration Logs

EAGLE QUANTUM PREMIER DEVICES12-21EAGLE QUANTUM PREMIER DEVICESVersion 6.0Oi Test FaultThe detector automatically conducts Oi tests to check t

Seite 43 - CALIBRATION LOGS

12-22EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESAlarm LED LatchThe tri-color LED on the face of the detector turns red when

Seite 44 - Calibration Logs

EAGLE QUANTUM PREMIER DEVICES12-23EAGLE QUANTUM PREMIER DEVICESVersion 6.0Alarms Selecting this button opens the “Alarms to Monitor...” dialog

Seite 45

12-24EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESPoint DisplayThe MIR X3302 has a custom “Point Display” that can be accessed

Seite 46 - PREFERENCES

1-5INSTALLATIONVersion 6.0ArchitectureThe S3 software suite is divided into two distinct environments, Configuration and Online Monitoring. The Config

Seite 47

EAGLE QUANTUM PREMIER DEVICES12-25EAGLE QUANTUM PREMIER DEVICESVersion 6.0X9800Infrared Flame DetectorThe IR X9800 is located on the LON/SLC and provi

Seite 48

12-26EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESConfigurationEnter the tagname for the detector, a miscellaneous description

Seite 49

EAGLE QUANTUM PREMIER DEVICES12-27EAGLE QUANTUM PREMIER DEVICESVersion 6.0Automatic OiThe IR X9800 includes the Automatic Optical Integrity (O

Seite 50

12-28EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESOi ConfigurationThe frequency of Oi testing can be adjusted between once a

Seite 51

EAGLE QUANTUM PREMIER DEVICES12-29EAGLE QUANTUM PREMIER DEVICESVersion 6.0Alarm LatchingThis refers to the fire alarm “message” being sent from the det

Seite 52

12-30EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESAlarmsSelecting this button opens the “Alarms to Monitor...” dialog box. Th

Seite 53

EAGLE QUANTUM PREMIER DEVICES12-31EAGLE QUANTUM PREMIER DEVICESVersion 6.0Point DisplayThe IR X9800 has a custom “Point Display” that can be accessed

Seite 54

12-32EAGLE QUANTUM PREMIER DEVICESPAGE LEFT BLANK INTENTIONALLYEAGLE QUANTUM PREMIER DEVICES

Seite 55

12-33EAGLE QUANTUM PREMIER DEVICESVersion 6.0X5200Ultraviolet (UV) / Infrared (IR) Flame DetectorThe UVIR X5200 is located on the LON/SLC and provides

Seite 56

12-34EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESThe optional description entered in the miscellaneous text field can be used

Seite 57

1-6INSTALLATIONVersion 6.0Online EnvironmentThe S3 software suite consists of a number of separate application programs that work togeth

Seite 58

EAGLE QUANTUM PREMIER DEVICES12-35EAGLE QUANTUM PREMIER DEVICESVersion 6.0Standard Signal ProcessingStandard signal processing is recommended for high

Seite 59

12-36EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESSensor Sensitivity Adjustments Both the UV and IR sensors have indiv

Seite 60

EAGLE QUANTUM PREMIER DEVICES12-37EAGLE QUANTUM PREMIER DEVICESVersion 6.0Oi ModeThe UVIR X5200 includes the Automatic Optical Integrity (Oi) feature

Seite 61

12-38EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESAlarms Selecting this button opens the “Alarms to Monitor...” dialog

Seite 62

EAGLE QUANTUM PREMIER DEVICES12-39EAGLE QUANTUM PREMIER DEVICESVersion 6.0Point DisplayThe UVIR X5200 detector has a custom “Point Display” that can b

Seite 63

12-40EAGLE QUANTUM PREMIER DEVICESPAGE LEFT BLANK INTENTIONALLYEAGLE QUANTUM PREMIER DEVICES

Seite 64

12-41EAGLE QUANTUM PREMIER DEVICESVersion 6.0X2200Ultraviolet (UV) Flame DetectorThe UV X2200 is located on the LON/SLC and provides Multi-Spectrum In

Seite 65

12-42EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESSignal Processing OptionsThe UV flame detector output (measured in counts per

Seite 66 - BACKUP/RESTORE

EAGLE QUANTUM PREMIER DEVICES12-43EAGLE QUANTUM PREMIER DEVICESVersion 6.0Automatic OiThe UV X2200 includes the Automatic Optical Integrity (O

Seite 67

12-44EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESSensitivity and Arc RejectionThe detector sensitivity and arc rejection se

Seite 68

1-7INSTALLATIONVersion 6.0DevelopmentThe “Development” installation does not install the low level security features of the “Operations” version. Use

Seite 69

EAGLE QUANTUM PREMIER DEVICES12-45EAGLE QUANTUM PREMIER DEVICESVersion 6.0Alarms Selecting this button opens the “Alarms to Monitor...” dialog box. T

Seite 70

12-46EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESPoint Display The UV Flame Detector (X2200) has a custom “Point Display” tha

Seite 71

EAGLE QUANTUM PREMIER DEVICES12-47EAGLE QUANTUM PREMIER DEVICESVersion 6.0EQ2200UVUltraviolet (UV) Flame DetectorThe UV EQ2200 is located on the LON/S

Seite 72 - OPC SERVER

12-48EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESThe UV flame detector output (measured in counts per second) is compared to t

Seite 73

EAGLE QUANTUM PREMIER DEVICES12-49EAGLE QUANTUM PREMIER DEVICESVersion 6.0Alarm Latching ModeThe red LED on the face of the detector comes on when in

Seite 74

12-50EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESPV DeadbandA field is provided to enter the desired PV (Process Variable) Dea

Seite 75

EAGLE QUANTUM PREMIER DEVICES12-51EAGLE QUANTUM PREMIER DEVICESVersion 6.0User LevelsThe “User Level Editor...” provides a means for limiting acces

Seite 76 - Security

PAGE LEFT BLANK INTENTIONALLY12-52EAGLE QUANTUM PREMIER DEVICES EAGLE QUANTUM PREMIER DEVICES

Seite 77 - Administrator Privileges

12-53EAGLE QUANTUM PREMIER DEVICESVersion 6.0EQ2200UVIRUltraviolet (UV)/Infrared (IR) Optical Flame DetectorThe UVIR EQ2200 is located on the L

Seite 78 - Creating User Accounts

12-54EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESTagnameThe tagname at the top of the dialog box refers to the flame detector

Seite 79 - Configure system enabled

1-8INSTALLATIONVersion 6.0Choose one of the two types of installations and click the Next button. A “Develolpment” install is required 3. when S3 is

Seite 80 - Restricted Access enabled

EAGLE QUANTUM PREMIER DEVICES12-55EAGLE QUANTUM PREMIER DEVICESVersion 6.0Standard Signal ProcessingStandard signal processing is recommended for high

Seite 81 - Passwords

12-56EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESAutomatic OiThe UVIR EQ2200 includes the Automatic Optical Integrity (Oi) fe

Seite 82

EAGLE QUANTUM PREMIER DEVICES12-57EAGLE QUANTUM PREMIER DEVICESVersion 6.0AlarmsSelecting this button opens the “Alarms to Monitor...” dialog b

Seite 83

12-58EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESPoint Display The UVIR EQ2200 has a custom “Point Display” that can be acce

Seite 84

EAGLE QUANTUM PREMIER DEVICES12-59EAGLE QUANTUM PREMIER DEVICESVersion 6.0PIRECLPoint IR Gas DetectorThe PIRECL is a diffusion based, point-type

Seite 85

12-60EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESGas TypeAfter entering the desired tagname and miscellaneous informati

Seite 86

EAGLE QUANTUM PREMIER DEVICES12-61EAGLE QUANTUM PREMIER DEVICESVersion 6.0Calibration Gas: Type and ConcentrationPIRECL supports three selections for

Seite 87

12-62EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESAlarm SetpointsThe High and Low gas alarm setpoints can be changed by enteri

Seite 88

EAGLE QUANTUM PREMIER DEVICES12-63EAGLE QUANTUM PREMIER DEVICESVersion 6.0AlarmsSelecting this button opens the “Alarms to Monitor...” dialog b

Seite 89

12-64EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESPoint DisplayThe Eclipse has a custom “Point Display” that can be

Seite 90

1-9INSTALLATIONVersion 6.0Verify that all options selected in previous windows are correct, use the Back button to make corrections, 5. choose Next to

Seite 91

EAGLE QUANTUM PREMIER DEVICES12-65EAGLE QUANTUM PREMIER DEVICESVersion 6.0OPECLOpen Path Eclipse Gas DetectorNOTEController Firmware 7 is required in

Seite 92

12-66EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESGas TypeAfter entering the desired tagname and miscellaneous informati

Seite 93

EAGLE QUANTUM PREMIER DEVICES12-67EAGLE QUANTUM PREMIER DEVICESVersion 6.0Alarm SetpointsThe High and Low gas alarm setpoints can be changed by enteri

Seite 94

12-68EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESAlarmsSelecting this button opens the “Alarms to Monitor...” dialog b

Seite 95

EAGLE QUANTUM PREMIER DEVICES12-69EAGLE QUANTUM PREMIER DEVICESVersion 6.0Point DisplayThe Open Path Eclipse has a custom “Point Display” that can be

Seite 96

PAGE LEFT BLANK INTENTIONALLY12-70EAGLE QUANTUM PREMIER DEVICES EAGLE QUANTUM PREMIER DEVICES

Seite 97

12-71EAGLE QUANTUM PREMIER DEVICESVersion 6.0Digital Communication Unit (DCU)For gas detectors and other analog inputsDCU’s are single channel analog

Seite 98

12-72EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESFrom a configuration standpoint, all DCU’s have the same basic adju

Seite 99

EAGLE QUANTUM PREMIER DEVICES12-73EAGLE QUANTUM PREMIER DEVICESVersion 6.0AlarmsSelecting this button opens the “Alarms to Monitor...” dialog b

Seite 100 - EAGLE QUANTUM PREMIER CONFIG

12-74EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESPoint DisplayThe DCU has a custom “Point Display” that can be accessed from

Seite 101

1-10INSTALLATIONVersion 6.0Hardware KeysA hardware key which attaches to the workstation determines the options that will be enabled on

Seite 102

EAGLE QUANTUM PREMIER DEVICES12-75EAGLE QUANTUM PREMIER DEVICESVersion 6.0Discrete IO (DCIO)/ Enhanced Discrete IO SIL (EDIO)Flexible 8 channel input/

Seite 103

12-76EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESDCIO/EDIO • STATIC LOGICTagnameThe tagname at the top of the dialog box refe

Seite 104

EAGLE QUANTUM PREMIER DEVICES12-77EAGLE QUANTUM PREMIER DEVICESVersion 6.0Static Logic Mode (Input)If the channel is configured as an input, a pull dow

Seite 105

12-78EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESThe first 13 alarms pertain to the status and diagnostic for the overall modu

Seite 106

EAGLE QUANTUM PREMIER DEVICES12-79EAGLE QUANTUM PREMIER DEVICESVersion 6.0DCIO/EDIO • USER LEVELSPoint DisplayThe DCIO has a custom “Point Displ

Seite 107

12-80EAGLE QUANTUM PREMIER DEVICESPAGE LEFT BLANK INTENTIONALLYEAGLE QUANTUM PREMIER DEVICES

Seite 108

12-81EAGLE QUANTUM PREMIER DEVICESVersion 6.0Intelligent Protection Module (IPM)8 channel input/output module for 24 Vdc discrete field devicesThe Int

Seite 109

12-82EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESTagnameThe tagname at the top of the dialog box refers to the entire module.

Seite 110

EAGLE QUANTUM PREMIER DEVICES12-83EAGLE QUANTUM PREMIER DEVICESVersion 6.0Abort ModeThe IPM abort input, Channel 1, is software configurable to use any

Seite 111

12-84EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESAlarm ConditionSingle Zone ModeUpon receipt of an alarm from an activated de

Seite 112

T-1Version 6.0CONTENTSSection 1 - IntroductionWarranty Information ... 1-1What is S3 . . .

Seite 113

2-1S3 CONFIGURATIONVersion 6.0When the S3 application program is started it will display its “MAIN SCREEN”. From this screen there is access to all t

Seite 114

EAGLE QUANTUM PREMIER DEVICES12-85EAGLE QUANTUM PREMIER DEVICESVersion 6.0Single Zone ModeThe signaling circuit can be configured to any standard SAM s

Seite 115

12-86EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESController OnlyIn this mode the I/O of the IPM will be controlled from the E

Seite 116 - EAGLE QUANTUM PREMIER DEVICES

EAGLE QUANTUM PREMIER DEVICES12-87EAGLE QUANTUM PREMIER DEVICESVersion 6.0The first 14 alarms pertain to the status and diagnostic for the overall modu

Seite 117

12-88EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESANALOG INPUT MODULE (AIM)Point DisplayThe IPM has a custom “Point Display” t

Seite 118

EAGLE QUANTUM PREMIER DEVICES12-89EAGLE QUANTUM PREMIER DEVICESVersion 6.0Analog Input Module (AIM)8 channel input module for 0-24 ma signalsAIM’s are

Seite 119

12-90EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESChannel ConfigurationAdjustable parameters include the engineering units and

Seite 120

EAGLE QUANTUM PREMIER DEVICES12-91EAGLE QUANTUM PREMIER DEVICESVersion 6.0Alarm Trigger DirectionIn addition, each alarm has a checkbox to cho

Seite 121

12-92EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESAIM • USER LEVELSThe first 12 alarms pertain to the status and diagnostic for

Seite 122

EAGLE QUANTUM PREMIER DEVICES12-93EAGLE QUANTUM PREMIER DEVICESVersion 6.0Completing ConfigurationWhen all parameters have been set, select the OK but

Seite 123

12-94EAGLE QUANTUM PREMIER DEVICESPAGE LEFT BLANK INTENTIONALLYEAGLE QUANTUM PREMIER DEVICES

Seite 124

2-2S3 CONFIGURATIONVersion 6.0PortsProvides access to the “Port Configuration” screen. From that screen up to ten (10) ports can be configured for acce

Seite 125

12-95EAGLE QUANTUM PREMIER DEVICESVersion 6.0Relay Module8 channel relay moduleThe 8 Channel Relay Module consists of eight individually configured out

Seite 126

12-96EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESDescription This field provides an area to describe the function of each rel

Seite 127

EAGLE QUANTUM PREMIER DEVICES12-97EAGLE QUANTUM PREMIER DEVICESVersion 6.0The first 13 alarms pertain to the status and diagnostic for the overall modu

Seite 128

12-98EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESPoint DisplayThe IPM has a custom “Point Display” that can be accessed from

Seite 129

EAGLE QUANTUM PREMIER DEVICES12-99EAGLE QUANTUM PREMIER DEVICESVersion 6.0RELAY MODULE • POINT DISPLAYAgent Release Module (ARM)The EQ2500ARM Series A

Seite 130

12-100EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESMode ControlARM outputs can be latching or non-latching. Non-latching foll

Seite 131

EAGLE QUANTUM PREMIER DEVICES12-101EAGLE QUANTUM PREMIER DEVICESVersion 6.0ARM • MODE CONTROLPoint DisplayThe ARM has a custom “Point Display” that ca

Seite 132

12-102EAGLE QUANTUM PREMIER DEVICESPAGE LEFT BLANK INTENTIONALLYEAGLE QUANTUM PREMIER DEVICES

Seite 133

12-103EAGLE QUANTUM PREMIER DEVICESVersion 6.0IDC2 channel Initiating Device Circuit (IDC) moduleThe EQ22xxIDC Series Initiating Device Circuit (IDC)

Seite 134

12-104EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESTagnameThe tagname at the top of the dialog box refers to the entire module

Seite 135

2-3S3 CONFIGURATIONVersion 6.0BackupsProvides access to the project backup and restore utility. This automated utility allows a selected p

Seite 136

EAGLE QUANTUM PREMIER DEVICES12-105EAGLE QUANTUM PREMIER DEVICESVersion 6.0If a static logic function has been selected for an input, when the input i

Seite 137

12-106EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESUser LevelsThe “User Level Editor...” provides a means for limiting access

Seite 138

EAGLE QUANTUM PREMIER DEVICES12-107EAGLE QUANTUM PREMIER DEVICESVersion 6.0SIGNAL AUDIBLE MODULE (SAM)Signal Audible Module (SAM)The EQ2500SAM Signal

Seite 139

12-108EAGLE QUANTUM PREMIER DEVICESVersion 6.0EAGLE QUANTUM PREMIER DEVICESTagnameThe tagname at the top of the dialog box refers to the module. Each

Seite 140

EAGLE QUANTUM PREMIER DEVICES12-109EAGLE QUANTUM PREMIER DEVICESVersion 6.0SAM • USER LEVELSUser LevelsThe “User Level Editor...” provides a mean

Seite 141

12-110EAGLE QUANTUM PREMIER DEVICESVersion 6.0Alarm LogsThe upper right quadrant of the point display shows the last eight alarms that have occurred a

Seite 142

13-1EQP LOGIC EDITORVersion 6.0Logic EditorThe Eagle Quantum Premier controller is a programmable device that requires a “user program” to be written

Seite 143

13-2EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITOROnce the “Logic” button is selected from the “Configure a controller ...” dialog box, the “Logic Editor”

Seite 144

EQP LOGIC EDITOR13-3EQP LOGIC EDITORVersion 6.0File MenuThis menu contains the standard “Windows” routines for setting up to print to a net

Seite 145

13-4EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITOREdit MenuThis menu contains the standard “Windows” routines for Cut, Copy and Paste that will be used t

Seite 146

2-4S3 CONFIGURATIONPAGE LEFT BLANK INTENTIONALLY

Seite 147

EQP LOGIC EDITOR13-5EQP LOGIC EDITORVersion 6.0In this sample find, the listed Element is “Fire Logic” which is a program, the Sheet Name in the logic

Seite 148

13-6EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORShow Line MarksIn the logic editor when a line is selected by clicking on it, or, when the “Connection

Seite 149

EQP LOGIC EDITOR13-7EQP LOGIC EDITORVersion 6.0Minimize I/O windows on startThis option is used to control the look and feel of the logic s

Seite 150

13-8EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORCompress and D/L projectWhen enabled the complete project is compressed and downloaded to the controlle

Seite 151

EQP LOGIC EDITOR13-9EQP LOGIC EDITORVersion 6.0Once created, this global memory point will be available in the logic editor for use as an input to or

Seite 152

13-10EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORLocal MemoryThis menu item opens the “Local Memory Editor...” which allows for the creation

Seite 153

EQP LOGIC EDITOR13-11EQP LOGIC EDITORVersion 6.0AB MonitorThis dialog box is a tool for checking the value of data in any of the eight configurable

Seite 154

13-12EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORIn the example below the AB address “B20/0” is configured to be moved to a Premier controller global va

Seite 155

EQP LOGIC EDITOR13-13EQP LOGIC EDITORVersion 6.0In the example to the right, the “LON” item has been expanded by clicking on the “+” sign and now show

Seite 156

13-14EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORAB Table SettingsThis menu selection opens a dialog box which allows up to eight communication interfa

Seite 157

3-1PORTSVersion 6.0Basic Port ConfigurationClicking on the “Ports” button from the S3 Navigation screen of the S3 software brings up the Port Configura

Seite 158

EQP LOGIC EDITOR13-15EQP LOGIC EDITORVersion 6.0MODBUS MovesThis dialog box allows for the configuration of data moving between a “Modbus RTU Master” s

Seite 159

13-16EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORIn the example below the MB address “00001” is configured to be moved to a Premier controller global va

Seite 160

EQP LOGIC EDITOR13-17EQP LOGIC EDITORVersion 6.0Tab 1Is for “Coils” which typically represent “Outputs” in a Modbus PLC. Coil addresses s

Seite 161

13-18EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORIn the example to the right, the “LON” item has been expanded by clicking on the “+” sign

Seite 162

EQP LOGIC EDITOR13-19EQP LOGIC EDITORVersion 6.0MODBUS Table SettingsThis menu selection opens a dialog box which shows the three communication interf

Seite 163

13-20EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORMove Up/Move DownThe Premier Controller executes its logic programs in the order that they appear in t

Seite 164

EQP LOGIC EDITOR13-21EQP LOGIC EDITORVersion 6.0NewThis button opens the “Element type selection” dialog box used to configure a newly created element.

Seite 165

13-22EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORSelect the “OK” button to return to the “Project Directory...” dialog box and the information on the n

Seite 166

EQP LOGIC EDITOR13-23EQP LOGIC EDITORVersion 6.0EnabledThe enabled checkbox determines whether the program will be executed by the controller or not.

Seite 167 - PAGE LEFT BLANK INTENTIONALLY

13-24EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORDuplicateThis button will make a copy of a selected element and add it to the project directory. When

Seite 168

3-2PORTSVersion 6.0The available choices are based on the S3 hardware key plugged into the computer, and only supported systems or devices are darkene

Seite 169

EQP LOGIC EDITOR13-25EQP LOGIC EDITORVersion 6.0ExportIf a function block or function is highlighted in the project directory window, the “Export” b

Seite 170

13-26EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORThe build process allocates memory, validates tagnames, validates data types, etc. View the “Errors/Wa

Seite 171

EQP LOGIC EDITOR13-27EQP LOGIC EDITORVersion 6.0Show Errors/WarningsThis menu selection opens the viewer and displays any problems found in

Seite 172

13-28EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORCheck Function BlockWhen a function block is open for editing, this menu item becomes available. When

Seite 173

EQP LOGIC EDITOR13-29EQP LOGIC EDITORVersion 6.0SimulateIf the project has been “built” and no errors were discovered then the program can be sim

Seite 174

13-30EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORSheets MenuThe S3 logic editor utilizes a Computer Aided Design (CAD) style of program to create logic

Seite 175

EQP LOGIC EDITOR13-31EQP LOGIC EDITORVersion 6.0SettingsThis menu item opens a dialog box where logic pages are given a “title” that appears in the ti

Seite 176

13-32EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORDuplicateThis button will create a new sheet at the end of the list of existing sheets. This “duplica

Seite 177

EQP LOGIC EDITOR13-33EQP LOGIC EDITORVersion 6.0Title BlocksIn the lower right area of each drawing sheet is a “Title Block” area which

Seite 178

13-34EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORNext/PreviousThese menu items become active whenever an element has more than one logic sheet. They c

Seite 179

3-3PORTSVersion 6.0PORT CONFIGURATIONSerial Port SettingsOnce the port type has been selected, the button face will change to match the selection. In

Seite 180

EQP LOGIC EDITOR13-35EQP LOGIC EDITORVersion 6.0In the example below, a single variable is being created, the tagname “UV Counts” has be

Seite 181

13-36EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORIn the example below the creation of local variable #1 “UV Counts” has been completed and there a

Seite 182

EQP LOGIC EDITOR13-37EQP LOGIC EDITORVersion 6.0Project ToolbarThis toolbar provides three shortcuts; Project Directory, Save Project and Build Projec

Seite 183

13-38EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORPointer ToolThis arrow shaped tool is used to select and manipulate the position and or size of any lo

Seite 184

EQP LOGIC EDITOR13-39EQP LOGIC EDITORVersion 6.0Input VariableAll input variables to a program or function are via this symbol. Once placed on a logi

Seite 185

13-40EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORSheet ToolbarThere are four icons which provide shortcuts to menu items having to do with logic sheets

Seite 186

EQP LOGIC EDITOR13-41EQP LOGIC EDITORVersion 6.0Control Panel ToolbarThere are three icons which provide shortcuts to menu items having to do with log

Seite 187

13-42EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORHelp MenuThe help menu provides access to the online help system and has two areas; “Standard Function

Seite 188

EQP LOGIC EDITOR13-43EQP LOGIC EDITORVersion 6.0In the example below, the “Absolute” function was selected and the details of how to us

Seite 189

PAGE LEFT BLANK INTENTIONALLY13-44EQP LOGIC EDITOREQP LOGIC EDITOR

Seite 190

3-4PORTSVersion 6.0The “Timers” button will open a dialog box allowing the “Polling” and “Watchdog” timers for the port to be set. There are also che

Seite 191

13-45EQP LOGIC EDITORVersion 6.0Logic CreationThe S3 Logic Editor provides a modern full featured IEC-61131-3 style environment to generate, test and

Seite 192

13-46EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORDefinitionsProgramsPrograms are the highest-level executable elements within an S3 project.

Seite 193

EQP LOGIC EDITOR13-47EQP LOGIC EDITORVersion 6.0The “Gate Settings...” dialog box provides a scrolling pull-down menu from which the number of

Seite 194

13-48EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORPlacing Logic Operators on a SheetTo develop a program the user must be able to use the Logic Editor t

Seite 195

EQP LOGIC EDITOR13-49EQP LOGIC EDITORVersion 6.0Select 6. NOT and click “OK”.The cursor will change to a miniature function block symbol when positio

Seite 196

13-50EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITOROnce this connection is established, the input variable can be repositioned anywhere left of its conne

Seite 197

EQP LOGIC EDITOR13-51EQP LOGIC EDITORVersion 6.0The “Input Selection...” dialog box presents the database as a hierarchical list of sources. Any item

Seite 198

13-52EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORThe final step in completing the example network is to link the NOT gates output variable to an appropr

Seite 199

EQP LOGIC EDITOR13-53EQP LOGIC EDITORVersion 6.0Wire-on-WireThis type of connection is used when a single signal needs to be routed to

Seite 200

13-54EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORClick to and drag to make the connection and create a wire. Draw the wire from the initial wire-to-wi

Seite 201

4-1START MONITORINGVersion 6.0Online OperationThe “Start Monitoring” button launches the DCD, which allows the user to access “Online Mode”.Online mod

Seite 202

EQP LOGIC EDITOR13-55EQP LOGIC EDITORVersion 6.0Combining the techniques described in the last few pages with the comprehensive standard set of S3 fun

Seite 203

13-56EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORIn the example to the below, an Input Variable was placed and linked to a global memory point “MCOP-FA

Seite 204

EQP LOGIC EDITOR13-57EQP LOGIC EDITORVersion 6.0Creating a SIL 2 projectAs specified by IEC 61508 there are 4 levels of safety performance necessary fo

Seite 205

13-58EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITOROnce the controller is set as a “SIL Controller” and a SIL device is chosen, the screen should look si

Seite 206

EQP LOGIC EDITOR13-59EQP LOGIC EDITORVersion 6.0SIL 2 LOGICSIL 2 LOGICNot SIL 2 compliant. There are non-red colored inputs and outputs.SIL 2 complian

Seite 207

13-60EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORSIL 2 LOGIC • FUNCTIONSCategoriesThe categories have the following meanings: SILThis item is SIL by s

Seite 208

EQP LOGIC EDITOR13-61EQP LOGIC EDITORVersion 6.0Functions SIL 2 LOGIC • FUNCTIONSGate/Function Name Logic Function Category NotesABS ABSOLUTE MutableA

Seite 209

13-62EQP LOGIC EDITORVersion 6.0EQP LOGIC EDITORColoringsAlways •REDAlways •BLACKAlways •BLACKRED if SIL controller, BLACK •otherwiseRED if SIL co

Seite 210

EQP LOGIC EDITOR13-63EQP LOGIC EDITORVersion 6.0SIL 2 LOGIC • FUNCTIONSSIL 2 LOGIC • FUNCTIONSLogic Function Category NotesABSOLUTE MutableACCESS ALAR

Seite 211

13-64EQP LOGIC EDITORVersion 6.0SIL 2 LOGIC • FUNCTIONSLogic Function Category NotesMINIMUM MutableMODBUS READNoMODBUS WRITENoMODULOYes See div, not c

Seite 212

4-2START MONITORINGVersion 6.0Shows the user detailed information about a selected TAG object. Each type of device, digital inputs, ana

Seite 213

EQP LOGIC EDITOR13-65EQP LOGIC EDITORVersion 6.0SIL 2 LOGIC • FUNCTIONSSIL 2 LOGIC • FUNCTIONSDevice Items ReferenceAs described earlier, inputs and

Seite 214

13-66EQP LOGIC EDITORVersion 6.0Item DescriptionsItem 1 - Firmware ID StringThe controller automatically polls LON devices for an ID string. The ID s

Seite 215

13-67EQP LOGIC EDITORVersion 6.0DEVICE ITEM NUMBER DESCRIPTIONSItem 7 - Device CodeEach device type has a unique code associated with it. Control

Seite 216

13-68EQP LOGIC EDITORVersion 6.0Item 11 - Time and Date of ConfigurationThe time and date of the configuration information is saved in this variable.It

Seite 217

13-69EQP LOGIC EDITORVersion 6.0Item 17 - Current Time and DateThe controller real time clock can be set or read with this variable.Item 18 - User Nam

Seite 218

13-70EQP LOGIC EDITORVersion 6.0Item 25 - Beeper VolumeThe volume level of the internal beeper can be adjusted with this variable. Values from 1 (low

Seite 219

13-71EQP LOGIC EDITORVersion 6.0Item 30 - Gas ModeGas Mode is used to determine if static logic should activate high and low gas alarms. When mode 1 i

Seite 220

13-72EQP LOGIC EDITORVersion 6.0DEVICE ITEM NUMBER DESCRIPTIONSItem 38 - Input Static Logic ModeInput mode is used to determine if static logic should

Seite 221

13-73EQP LOGIC EDITORVersion 6.0Item 43 - Oi ModeOptical Integrity mode can be selected with this variable. Oi ModeValueDenition0Automatic1Manual It

Seite 222

13-74EQP LOGIC EDITORVersion 6.0Item 49 - IR Oi Test FrequencyThree consecutive failures are required to fault, and three consecutive good tests are r

Seite 223

T-2Version 6.0CONTENTSSection 6 - LogsOverview of features... 6-1Alarm Logs (DCD Disk Log)

Seite 224

4-3START MONITORINGVersion 6.0ONLINE FKEY FEATURESAcknowledge (F3)Silences audible alarms, causes all TAG objects in a “New Alarm” state on the graphi

Seite 225

13-75EQP LOGIC EDITORVersion 6.0Item 54 - Calibration Gas TypeCalibration gas type is selected with this code.Description ModeSame as Measured (Defaul

Seite 226 - EQP LOGIC EDITOR

13-76EQP LOGIC EDITORVersion 6.0DEVICE ITEM NUMBER DESCRIPTIONSItem 66 - Alternate FunctionEach of the controller I/O points has a predefined alternate

Seite 227

13-77EQP LOGIC EDITORVersion 6.0Item 79 - CPU FaultThe item indicates a problem with a processor or memory system, the cause of this fault is device d

Seite 228

13-78EQP LOGIC EDITORVersion 6.0Item 91 - Flame Detector Counts per SecondThis variable represents the counts per second from flame detectors.Item 92 -

Seite 229

13-79EQP LOGIC EDITORVersion 6.0Item 102 - LON B Interface FaultThe bit is set when a problem is detected with LON interface channel B.Item 103 - Inhi

Seite 230

13-80EQP LOGIC EDITORVersion 6.0Item 113 - Com 1 FaultEach field device contains two network relays used to isolate network wiring faults. A status it

Seite 231

13-81EQP LOGIC EDITORVersion 6.0Item 128 - Sensor Initialization FaultThe field device sets the item to indicate that the sensor was bad at start-up.

Seite 232

13-82EQP LOGIC EDITORVersion 6.0A device sets this item to indicate that the optics need to be cleaned.Item 142 - Internal Comm FaultA device sets thi

Seite 233

13-83EQP LOGIC EDITORVersion 6.0Item 150 - Inhibit ControlSetting this control item instructs the controller to inhibit the device or channel associat

Seite 234

13-84EQP LOGIC EDITORVersion 6.0Item 152 - Activate ResetSetting this control item instructs the controller to send a reset command to the field device

Seite 235

4-4START MONITORINGVersion 6.0Alarm History (F6)Opens the “Alarm History” screen and displays the current days log. This daily log shows date and tim

Seite 236

13-85EQP LOGIC EDITORVersion 6.0Item 165 - Activate Low Gas AlarmSetting this control item in the controller activates the low gas alarm output. Item

Seite 237

13-86EQP LOGIC EDITORVersion 6.0Item 179 - Activate SupervisorySetting this control bit activates the controller supervisory output, status bit and LE

Seite 238

13-87EQP LOGIC EDITORVersion 6.0Item 195 - No Oi High Energy FaultA field device sets this status bit to indicate that the No Oi High Energy Fault is t

Seite 239

13-88EQP LOGIC EDITORVersion 6.0Item 222 - Request TemperatureSetting this control bit will cause the controller to retrieve the temperature from a de

Seite 240

13-89EQP LOGIC EDITORVersion 6.0Item 254 - Missed MessagesThe number of times that an incoming packet was discarded because there was no network buffe

Seite 241

13-90EQP LOGIC EDITORVersion 6.0Item 268 - UV Oi Calibration FaultThis item comes true when an UV Oi calibration fault occurs. The UV Oi lamp is activ

Seite 242

13-91EQP LOGIC EDITORVersion 6.0Item 279 - mA Range LowThis value defines the low/zero point for a 4 to 20 mA input channel expressed in mAs. Typical

Seite 243

13-92EQP LOGIC EDITORVersion 6.0Item 291 - Redundancy Fault CodeThis item can be used to determine the cause of a Redundancy fault.CodeDescription0No

Seite 244

13-93EQP LOGIC EDITORVersion 6.0Item 295 - Smoke Detector TypeThis item selects a type of smoke detector.ValueDetector Type0Invalid1Apollo2FenwalItem

Seite 245

13-94EQP LOGIC EDITORVersion 6.0Item 298 - Control ModeThis item selects the embedded logic control mode.ValueMode0Invalid1Embedded Logic Only2Control

Seite 246

4-5START MONITORINGVersion 6.0Port Diagnostics (F11)Opens the “Port Diagnostics” screen which displays the status of all ten communication ports. Dyn

Seite 247

13-95EQP LOGIC EDITORVersion 6.0Item 309 - One Zone Bell ToneThis item is used to select the bell tone when one zone of the IPM is in alarm and emb

Seite 248

13-96EQP LOGIC EDITORVersion 6.0Item 314 - Serial Port 2 ParityThe parity setting for the second configurable serial port is set with this variable. Th

Seite 249

13-97EQP LOGIC EDITORVersion 6.0Item 321 - Serial Port 4 Baud RateSerial baud rate for serial port 3 is set with this variable. The allowed selection

Seite 250

13-98EQP LOGIC EDITORVersion 6.0Item 333 - Lon Overload FaultThis item is used to indicate that user logic is attempting to write more data to LON out

Seite 251

13-99EQP LOGIC EDITORVersion 6.0Item 343 - Suppression TimerFirst used with the Automotive MIR Flame Detector (X3301). Refer to the AMIR X3301 specific

Seite 252

13-100EQP LOGIC EDITORVersion 6.0Item 352 - Controller Inhibit ModeIn Alarms only mode, the inhibit feature inhibits only the alarms. The Alarms and

Seite 253

13-101EQP LOGIC EDITORVersion 6.0Item 361 - Beam Block DelayThe beam block delay is used with Open Path. This is the amount of time that must go by be

Seite 254

Detector Electronics Corporation6901 West 110th Street Minneapolis, MN 55438 USAT: 952.941.5665 or 800.765.3473F: 952.829.8750W: http://www.det-troni

Seite 255

4-6START MONITORINGVersion 6.0Data TablesThe data tables show users the current information about addresses and bits being read from attached sys

Seite 256

4-7START MONITORINGVersion 6.0LON OverviewThis is a specialized diagnostic screen which displays a schematic representation of the addres

Seite 257

PAGE LEFT BLANK INTENTIONALLY4-8START MONITORING

Seite 258

5-1PRINTINGVersion 6.0Overview of featuresUsing the Windows default local or network printer, S3 can be print comprehensive documentation of port, poi

Seite 259

5-2PRINTINGVersion 6.0Filtering data to be printedTagnames (All)This selection prints a list of all tagnames used in the system.User Module StringsThi

Seite 260

5-3PRINTINGVersion 6.0Selecting ports to documentPort 1 - 10S3 supports up to ten ports. Each port can be physical serial port or an Ethernet connect

Seite 261

5-4PRINTINGPAGE LEFT BLANK INTENTIONALLYPRINTING

Seite 262

T-3Version 6.0CONTENTSPoint Display ... 11-10Reset Module ...

Seite 263

6-1LOGSVersion 6.0Overview of featuresS3 maintains three different types of logs; disk, configuration and calibration. All can be viewed and printed f

Seite 264

6-2LOGSVersion 6.0Alarm Logs (DCD Disk Log)Below is a sample alarm log. Running down the right hand side is the log name (which is the date), navigat

Seite 265

6-3LOGSVersion 6.0Configuration LogsBelow is a sample configuration log. Running down the right hand side is the log name (which is the date), navigat

Seite 266

6-4LOGSVersion 6.0CALIBRATION LOGSThe Configuration and Alarm logs can be opened or viewed, and previous logs can be printed by using the “Select Log”

Seite 267

6-5LOGSVersion 6.0Calibration LogsBelow is a sample calibration log. The calibration log reporter is a configurable database query tool designed to all

Seite 268

6-6LOGSVersion 6.0Calibration Log Reporter Filter OptionsThe options button opens the “Filter Options..” dialog box allowing for the S3 database query

Seite 269

7-1PREFERENCESVersion 6.0The preferences button provides access to a variety of project management and global attributes and settings. They are acces

Seite 270

7-2PREFERENCESVersion 6.0Drawing (Unsupported Feature)The drawing tab allows for the setting of the default operation of two drawing tools in the grap

Seite 271

7-3PREFERENCESVersion 6.0ClockThe purpose of the clock tab is to accommodate the two different methods for displaying the time and date around th

Seite 272

7-4PREFERENCESVersion 6.0User StringsThe “User Strings” tab provides access to a very powerful feature, the Second Language Dictionary (SLD). The SLD

Seite 273

T-4Version 6.0CONTENTSMIR Flame Detector (X3301) ... 12-13Overview...

Seite 274

7-5PREFERENCESVersion 6.0ExamplesBelow is an example of EAGLE2000/Eagle Quantum SLD configuration. On the right hand side of the dialog box are a seri

Seite 275

7-6PREFERENCESVersion 6.0SLD descriptions for the user interface buttons used by the online application are presented in the “Factory Name” col

Seite 276

7-7PREFERENCESVersion 6.0“Miscellaneous Strings” are pieces of descriptive text used in a variety of online locations like dialog boxes, window na

Seite 277

7-8PREFERENCESVersion 6.0Graphics (Unsupported Feature)This category pertains to the operation of the “Online” application. This application displays

Seite 278

7-9PREFERENCESVersion 6.0Cyrillic FontS3 supports the use of Cyrillic in the SLD for both display and printing purposes when used with the recommended

Seite 279

7-10PREFERENCESVersion 6.0Visual Object Error Settings (Unsupported Feature) This checkbox selection enables an online feature that changes the color

Seite 280

7-11PREFERENCESVersion 6.0Choose from any of the 48 standard color definitions displayed, or from the 16 custom colors.Select the “Define Custom Colors”

Seite 281

7-12PREFERENCESVersion 6.0Color Depth SettingsThere are three choices for the displayed color depth, 16, 24 and 32. This corresponds to the maximum n

Seite 282

7-13PREFERENCESVersion 6.0PREFERENCES • LOGSPREFERENCES • GRAPHICSLogsThis tab allows the setting of the log retention time. This adjustment determin

Seite 283

7-14PREFERENCESVersion 6.0DCDThe Data Collector and Distributor application program has five configurable parameters that can be used to modify its beha

Seite 284

T-5Version 6.0CONTENTSUVIR Flame Detector (EQ2200UVIR)... 12-53Overview...

Seite 285

7-15PREFERENCESVersion 6.0Screen PrintsIn addition to capturing screens in S3, the captured screens can be sent to either a local or remote printer fo

Seite 286

7-16PREFERENCESVersion 6.0Screen SaverS3 provides a screen saver feature that will display the current time on a black background after a user configur

Seite 287

7-17PREFERENCESVersion 6.0Button User LevelsThis feature allows the DCD application program’s user interface buttons to be assigned a “User

Seite 288

7-18PREFERENCESVersion 6.0SoundsThe sounds tab allows access to the custom sounds database and integrated sound editor. Selecting the “Edit” button w

Seite 289

7-19PREFERENCESVersion 6.0The sound editor makes use of the standard Windows based sound card and microphone to allow for the recordi

Seite 290

PAGE LEFT BLANK INTENTIONALLY7-20PREFERENCESPREFERENCES • SOUNDS

Seite 291

8-1BACKUP/RESTOREVersion 6.0 Overview of featuresThis button provides access to S3’s built in project Backup and Restore utilities. Thes

Seite 292

8-2BACKUP/RESTOREVersion 6.0BackupOnce the project is selected a dialog box will be displayed allowing for browsing of the file system in order to sele

Seite 293

8-3BACKUP/RESTOREVersion 6.0After the files have been compressed they will be copied to the destination volume, the status will indica

Seite 294

8-4BACKUP/RESTOREVersion 6.0Once the disk is in place, choose the desired file option, either “Single” or “Multiple”. The default is “Single” and

Seite 295

T-6Version 6.0CONTENTSAnalog Input Module (AIM) ... 12-89Overview...

Seite 296

8-5BACKUP/RESTOREVersion 6.0RestoreTo restore an archived project from either a floppy disk or network, select the “Restore” button from the Backup/Res

Seite 297

8-6BACKUP/RESTOREVersion 6.0Once the project to be restored has been chosen and the “OK” button selected, the file system browser dialog box is display

Seite 298

9-1OPC SERVERVersion 6.0S3 is designed to simply and efficiently “integrate” data from a variety of multi-vendor safety solutions into a common Op

Seite 299

9-2OPC SERVERVersion 6.0OPC Server ConfigurationTo configure OPC data points, select the OPC Server button from the S3 Main Screen. This will display

Seite 300

9-3OPC SERVERVersion 6.0OPC Property ViewerThe properties button at the bottom of the OPC Server Configuration dialog box will open the “OPC Property V

Seite 301

9-4OPC SERVERPAGE LEFT BLANK INTENTIONALLY

Seite 302

10-1USER LOG IN & OUT/ACCOUNTSVersion 6.0SecurityThese buttons are part of the S3 security system. The “Log In/Out” button is used to log in or c

Seite 303

10-2USER LOG IN & OUT/ACCOUNTSVersion 6.0Administrator PrivilegesThe person logged in as the Administrator is the only one who can create, modify

Seite 304

10-3USER LOG IN & OUT/ACCOUNTSVersion 6.0Creating User AccountsTo create a new user, select the “New” button from the “User Settings” dialog box (

Seite 305

10-4USER LOG IN & OUT/ACCOUNTSVersion 6.0After entering the new users name, select “OK” to accept the name and display the “User settings...” dial

Seite 306

T-7Version 6.0CONTENTSModbus Monitor ... 13-14Modbus Moves ...

Seite 307

10-5USER LOG IN & OUT/ACCOUNTSVersion 6.0Port Diagnostics viewing enabledWhen selected, when online the user can access the port diagnostics scree

Seite 308

10-6USER LOG IN & OUT/ACCOUNTSVersion 6.0If “restricted access” is combined with “configure system” the user can also create project backups using

Seite 309

11-1EAGLE QUANTUM PREMIER CONFIG.Version 6.0EQP ConfigurationOne of the supported communication port types is for the Detector Electronics Corpo

Seite 310

11-2EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.Configuration ScreenThe main configuration screen is divided into two

Seite 311

EAGLE QUANTUM PREMIER CONFIG.11-3EAGLE QUANTUM PREMIER CONFIG.Version 6.0Command Bar OverviewThe command bar has fifteen buttons, most of which initiat

Seite 312

11-4EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.Get RevisionReturns the selected devices revision and firmware version informa

Seite 313

EAGLE QUANTUM PREMIER CONFIG.11-5EAGLE QUANTUM PREMIER CONFIG.Version 6.0GlobalsProvides access to configuration services allowing defined global memory

Seite 314

11-6EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.A dialog box labeled “Global Point Monitor Configuration...” that is specific t

Seite 315

EAGLE QUANTUM PREMIER CONFIG.11-7EAGLE QUANTUM PREMIER CONFIG.Version 6.0Discrete PointsGlobals tied to “discrete” ON/OFF type events can be set to al

Seite 316

11-8EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.Analog PointsGlobals tied to “analog” type events can be set to alarm in acco

Seite 318

EAGLE QUANTUM PREMIER CONFIG.11-9EAGLE QUANTUM PREMIER CONFIG.Version 6.0Once the event name is entered and the comparison configured, the even

Seite 319

11-10EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.Since hundreds of monitored global points can be created, a “Search” button

Seite 320

EAGLE QUANTUM PREMIER CONFIG.11-11EAGLE QUANTUM PREMIER CONFIG.Version 6.0In the example below Node 1, the Controller (EQ3001) is selected.When the “P

Seite 321

11-12EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.Reset ModuleThis command forces a selected field device to perform a “soft re

Seite 322

EAGLE QUANTUM PREMIER CONFIG.11-13EAGLE QUANTUM PREMIER CONFIG.Version 6.0LON DiagnosticDisplays a graphic “LON Schematic” displaying dynamic informat

Seite 323

11-14EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.Diagnostic data is displayed to two ways on the display, through the color o

Seite 324

EAGLE QUANTUM PREMIER CONFIG.11-15EAGLE QUANTUM PREMIER CONFIG.Version 6.0Point AddressAllows a node on the LON schematic to be given a different addr

Seite 325

11-16EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.EditSelecting the “Edit” button displays the detailed configuration data for

Seite 326

EAGLE QUANTUM PREMIER CONFIG.11-17EAGLE QUANTUM PREMIER CONFIG.Version 6.0Get VoltagesDisplays 24 Vdc supply voltage information for uses such as trou

Seite 327

11-18EAGLE QUANTUM PREMIER CONFIG.Version 6.0EAGLE QUANTUM PREMIER CONFIG.OutputsTags linked to commands to be sent to the controller or field devices

Verwandte Modelle: EQP Safety System Software