13-74
EQP LOGIC EDITOR
Version 6.0
Item 49 - IR Oi Test Frequency
Three consecutive failures are required to fault, and three consecutive good tests are required to return to normal.
While an IR oi fault is active the test frequency is reduced to once per minute.
IR Oi Test Frequency
Value
Denition
1
1 minute (Default)
2
1 Hour
3
2 Hours
4
4 Hours
Item 50 - Full Scale Value
The Engineering unit full scale value can be configured and must match the current rating of power supply
monitor. Only one model has been defined, 80 Amp, with a range of -16 Amps to +80 Amps.
Item 51 - AC Fault Threshold
The power supply monitor fault threshold can be set with this variable.
Item 52 - Supervision Option Select
An I/O channel can be configured with or without supervision.
Mode
Denition
1
No Supervision
2
Monitor for opens
3
Monitor for opens and shorts
Item 53 - Eclipse Gas Type
This field allows the PIRECL to be configured for different gas types.
Code
Description
1
Methane (Default)
2
Ethane
3
Propane
4
Ethylene
5
Propylene
6
Butane
7
Reserved
8
Reserved
9
Reserved
10
Special
DEVICE ITEM NUMBER DESCRIPTIONS