Det-tronics S3 Graphics Bedienungsanleitung Seite 222

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 327
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 221
EAGLE QUANTUM PREMIER DEVICES
12-107
EAGLE QUANTUM PREMIER DEVICES
Version 6.0
SIGNAL AUDIBLE MODULE (SAM)
Signal Audible Module (SAM)
The EQ2500SAM Signal Audible Module is located on the LON/SLC and provides NFPA-72 compliant Notification
Appliance Circuit (NAC) control capability to the Eagle Quantum Premier system.
The Signal Audible Module provides two indicating circuits for controlling UL Listed 24 Vdc polarized audible/
visual indicating appliances.
The device is located on the LON and is controlled by programmable logic in the Controller.
Each output circuit is independently programmable to allow notification of separate events.
Each output can be individually activated for any one of the following pre-defined outputs:
Continuous1.
60 beats per minute2.
120 beats per minute3.
Temporal pattern.4.
Device outputs operate in the reverse polarity manner when activated. Each output is rated at 2 amperes.
The output circuits are supervised for open and short circuit conditions.
If a wiring fault occurs, a trouble condition will be indicated at the Controller and on the S
3
Point Display.
Seitenansicht 221
1 2 ... 217 218 219 220 221 222 223 224 225 226 227 ... 326 327

Kommentare zu diesen Handbüchern

Keine Kommentare