13-101
EQP LOGIC EDITOR
Version 6.0
Item 361 - Beam Block Delay
The beam block delay is used with Open Path. This is the amount of time that must go by before a blocked beam
fault is declared. The delay is configurable from 1 minute to 60 minutes.
Item 362 - Standby Power Fault 1
The standby controller sets this status variable when low voltage is detected on the power input #1.
Item 363 - Standby Power Fault 2
The standby controller sets this status variable when low voltage is detected on the power input #2.
Item 364 - Standby LON Fault
The standby controller sets this item when a Lon fault is detected.
Item 365 - Standby LON Gnd Fault
When this item is true, the standby controller has detected a ground fault.
Item 366 - Standby Controller Fault
This item is true when the standby controller has been reset by a Watch Dog Reset.
Item 367 - HSSL Communication Fault
This item is true when the master controller loses communication with the standby controller.
DEVICE ITEM NUMBER DESCRIPTIONS
DEVICE ITEM NUMBER DESCRIPTIONS