Det-tronics S3 Graphics Bedienungsanleitung Seite 318

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 327
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 317
13-93
EQP LOGIC EDITOR
Version 6.0
Item 295 - Smoke Detector Type
This item selects a type of smoke detector.
Value
Detector Type
0
Invalid
1
Apollo
2
Fenwal
Item 296 - Abort Mode
This item selects the type of abort mode.
Value
Mode
0
Invalid
1
Mode 1
2
Mode 2
3
IRI Mode
Mode 1: Upon activation, timer will count down to and hold at 10 seconds; upon release, timer will continue to
count down to zero.
Only this mode complies with UL 864.
Mode 2: Upon activation, timer will reset to initial value; upon release, timer will continue to count down to zero.
IRI Mode: This function is similar to “Mode 1” with the exception that the abort will only function if held prior to
receiving the second alarm.
Item 297 - Detection Style
This item selects the Detection Style Single or Cross Zoned. When single zone is selected, a release is activated
if ether input is activated. Cross zone requires that both inputs be active before a release is activated.
Value
Mode
0
Invalid
1
Single Zone (1 zone
release)
2
Cross Zoned (2 zone
release)
DEVICE ITEM NUMBER DESCRIPTIONS
Seitenansicht 317
1 2 ... 313 314 315 316 317 318 319 320 321 322 323 ... 326 327

Kommentare zu diesen Handbüchern

Keine Kommentare